Engineered once, deployable many times.
A modular medical waste unit treats clinical waste at the point of care — sterilising infectious material in an autoclave and reducing volume through shredding before final disposal. structmod modular medical waste units serve hospitals managing their own clinical waste stream rather than relying on external disposal contractors, field hospitals operating in remote locations without established waste infrastructure, and humanitarian programmes treating waste in disaster or conflict settings. The modular unit handles the standard clinical waste streams — sharps, infectious soft waste, anatomical waste, pharmaceutical waste — through a combined autoclaving and shredding process that renders waste safe and reduces disposal volume by 70-80%.
The treatment workflow is engineered around safety and operator protection: clinical waste arrives at the unit in colour-coded bags or sharps bins per the segregation protocol; loading into the autoclave chamber happens through a sealed loading bay protecting the operator from exposure; the autoclave cycle (typically 134°C for 18 minutes or equivalent dwell time) sterilises all infectious material to log-6 reduction of bacterial spore challenges per EN 285 or ISO 17665; treated waste transfers to the integrated shredder reducing it to fragments under 25 mm; the shredded sterile output goes to standard municipal waste stream rather than requiring specialist clinical waste disposal. Operator protection includes PPE workflow, eyewash, emergency shower, and cycle-failure alarms.
structmod modular medical waste units deliver to hospitals seeking to internalise clinical waste management for cost or sovereignty reasons, to military and humanitarian field hospitals where external waste contractor services don't exist, to specialty facilities (research labs, clinical trial sites, burns units) generating high-volume specialist waste streams, and to national health programmes building distributed waste treatment infrastructure. Lead time is 10-12 weeks from contract signature. Compliance includes EN 285 / ISO 17665 autoclave validation, WHO Safe Management of Wastes from Health-Care Activities guidance, and EU Waste Framework Directive (2008/98/EC) for European deployments.
Tipik Konuşlanma Sırası
- Gün 1 — saha temeli doğrulandı, vida krikoları veya şerit temel yerleştirildi
- Gün 2–3 — modüller mobil vinçle konumuna yerleştirildi
- Gün 3–4 — modüller arası bağlantılar ve zarf sızdırmazlığı
- Gün 4–5 — MEP bağlantıları, ıslak testler
- Gün 5–6 — iç kaplama, armatür ve ekipman montajı
- Gün 7 — devreye alma, FAT raporu, kullanıcı eğitimi ve teslimat
Spec sheet — STR-2606
| Toplam uzunluk | 12.6 m · 41.3 ft |
|---|---|
| Genişlik (nakliye) | 2,99 m |
| Genişlik (konuşlandırılmış) | 2,99 m |
| Yükseklik (nakliye) | 2,90 m |
| Zemin alanı (konuşlandırılmış) | 37.7 m² |
| Boş ağırlık | 14.6 t |
| Şasi | EN 10025 S355JR sıcak hadde çelik · EN 1090 EXC-2 |
| Kaynak kalitesi | EN ISO 3834-3 |
| Zarf | Sandviç panel, PIR çekirdek 80 mm · λ ≈ 0,023 W/(m·K) |
| Yangın direnci | EI-30 · EN 13501-2'ye göre test edilmiş |
| Zemin | EPDM üzerine denizcilik kontrplak · R-10 kayma sınıfı |
| Elektrik tesisatı | 120/240 V · 60 Hz (ABD spec) · IEC 60364 uyumlu |
| İklimlendirme | Çatı üstü paket cihaz · MERV-13 |
| Çalışma aralığı | −25 °C ile +50 °C ortam |
| Rüzgar sınıfı | 150 km/s temel rüzgar için tasarlandı (EN 1991-1-4) |
| Sismik tasarım | EN 1998-1 (Eurokod 8) uyarınca · sünek sınıf DCM |
| Nakliye | ISO 668 ayak izi · CSC plakası uygun (konteyner varyantlar) |
| Kurulum süresi | 3 saat · 2 kişilik ekip |
Tam çizimler, hesap notları, DoP, İ&B kılavuzu ve FAT raporu her ünite ile dahildir. Özellikler gösterge niteliğindedir — proje gereksinimlerine göre yapılandırılabilir.